How 4–20 mA Scaling Works
Quando si applica
Use this guide when loops read correctly at the transmitter but HMI numbers disagree because span and zero were never written down.
Strumento da usare
Browser-based preliminary check for Four Twenty MA Converter — fast estimates, not code or stamped design output.
Apri Four Twenty MA Converter →Passaggi
- 1Confirm whether 4 mA represents live zero or indicates fault depending on device policy.
- 2Define engineering value at 4 mA and at 20 mA for the measured variable.
- 3Solve linear relationship between mA and engineering units.
- 4Cross-check mid-scale points with a calibrator if disputes persist.
- 5Document alarm thresholds with the same scaling basis.
Esempi
- Tank level 4 mA empty, 20 mA full.
- Pressure transmitter with elevated zero.
Cosa evitare
- Using raw mA in SCADA without engineering conversion.
- Confusing square-root relationships for orifice DP without configuring properly.
- Ignoring square-root extraction done inside the device vs in software.
Strumenti correlati
Sul blog
Altro in Ingegneria
- How to Calculate Pressure Drop in Pipes
- What Reynolds Number Means in Pipe Flow
- How Pump Affinity Laws Change Flow, Head, and Power
- How to Calculate Voltage Drop for Cable Runs
- Single-Phase vs Three-Phase Power Basics
- How to Estimate Dew Point
Tutte le guide per attività oppure l’elenco completo nel hub Ingegneria.
FAQ
HART digital values?
Digital PV may differ if secondary variables are addressed; verify which variable scales to mA.
Fault currents?
Some devices use <3.6 mA or >21 mA for fault; know your device.